PRODUCTS

 



 

 

Application:This product can be used in indoor system of 50Hz and rated voltage 7.2KV to 36kV. It can break the fault current between the min.interrupting current and the rated interrupting current. 

 





 

 

 

 

basic parameters

 

 

Rated voltage

Rated current of the fuse

Rated current of the fuse

Rated break current

12

63

1016202531.5405063

50

 

 

 

Selecting principles

 

 

   primary voltage of the transformer 12Kv

Transformer capacity KVA

Fuse rated current(A)

Fuse type

≤125

10

 

160

16

200-250

20

315

25

400

31.5

500

40

630

50

800

63

 

 

 

 

Installation Dimensions

 

 



Chat1/a link
ΦAΦ76mm 10-63A
Φ88mm 80-100A

 

 

 

 

 

 



Chat1/b link(KV)

 

 

 

 

 

 

 

 

Technique data

 

 

Type

Rated voltage(KV)

Fuse current(A)

d(mm)

Foreing counterparts

XRNT□

12

10

76

FFLAJ

16

20

31.5

40

50

63

80

88

 

100

 

 

 

 

 

 

 

 

Property curve diagram